§411.3 Protection by Automatic Disconnection of Supply — General Requirements EB SUMMARY
💡 Explain in plain words
This clause sets the general rule for automatic disconnection: protection must operate before the touch voltage exceeds the safe limit of 50 V AC. To achieve this, three things are coordinated — the fault loop impedance Zs, the characteristic of the protective device, and its operating current Ia. For TN systems, the main condition is simple: Zs × Ia ≤ U₀, meaning the loop must be sufficiently low-impedance so that the short-circuit current is high enough for the device to operate quickly. The standard specifies maximum disconnection times (Table 41.1): for final circuits up to 32 A at 230 V — no more than 0.4 s. In practice, this is why it is important to measure the loop impedance during commissioning — to ensure that the circuit breaker will actually disconnect in time.