§411.4 TN system — automatic power-off time
In a TN system, the source neutral is bonded to protective earth, so the L-PE fault current returns through a metallic loop from the fault point back to the source. Requirements apply to all TN subtypes — TN-C (PEN conductor), TN-S (separate PE and N), TN-C-S (combined/split section). This allows overcurrent protective devices (MCBs, fuses) as the primary means of automatic disconnection. **The condition must be met**: Z_s × I_a ≤ U_0, where Z_s is the total loop impedance, I_a is the protective device operating current, and U_0 is the nominal phase-to-earth voltage. For final circuits of stationary equipment up to 32 A (or 63 A for socket-outlet final circuits) at U_0 = 230 V AC, the maximum disconnection time is 0.4 s; for other nominal U_0 voltages (400 V AC, DC systems) — per Table 41.1. For distribution circuits and others outside this range, up to 5 s is allowed. If a specific product standard permits a longer disconnection time, that value applies. If the condition Z_s × I_a ≤ U_0 cannot be met (e.g., long cable runs), apply additional protection by an RCD ≤30 mA (§415.1) or supplementary equipotential bonding (§415.2). Verification of loop impedance at commissioning is key to confirming compliance.
EB-authored summary for design convenience — NOT normative IEC text. Official standard IEC 60364-4-41:2005+A1:2017 available at webstore.iec.ch →.
Explain in plain words
In plain words
AI-generated — may contain inaccuracies
In a TN system, the source neutral is earthed and connected to the protective conductor PE, so the fault current to the enclosure returns via a metallic loop and is high. Thanks to this, ordinary circuit breakers and fuses can serve as the main 'fault disconnector'. The condition is the same: Zs × Ia ≤ U₀. The disconnection time is standardized — 0.4 s for final circuits up to 32 A at 230 V and up to 5 s for distribution circuits. If the loop is too long and the condition is not met (e.g., long cable), an additional RCD ≤30 mA or supplementary equipotential bonding can help. The main practical takeaway: in TN, the correctness of protection is confirmed by measuring the 'phase–PE' loop impedance.