§411.5 TT-system — automatic power-off time
Explain in plain words
In a TT system, the equipment enclosure is earthed via its own local earth electrode, not metallically connected to the source earthing, so the fault current passes through the ground and is usually too low to reliably trip a circuit breaker. Therefore, in TT, the main protective device must be an RCD. The condition here is different: R_A × I_ΔN ≤ 50 V, where R_A is the resistance of the local earth electrode and I_ΔN is the rated residual operating current of the RCD; hence, the worse the earth electrode, the more sensitive the RCD must be. The disconnection time for final circuits is 0.2 s. In practice, for a TT installation, it is critical to install an RCD at the supply intake or on circuits and check the earth resistance and actual RCD operation using the 'Test' button and a tester during commissioning.