§411.6 IT-system — first fault withstand capability
Explain in plain words
The IT system is designed so that the first insulation fault does not interrupt operation — this is important for hospitals and continuous processes. The source neutral is either isolated from earth or connected via a high impedance, so the first fault to the enclosure produces only a small leakage current and the voltage on enclosures remains safe. Therefore, automatic disconnection after the first fault is not required, but an insulation monitoring device (IMD) must be installed to immediately give a signal so that personnel can locate and rectify the defect. Danger arises upon a second fault on a different phase — then protection (circuit breakers, RCDs) must disconnect within the standardized time. In practice: IT is rare in domestic installations, but if you maintain one — the main thing is not to ignore the IMD signal, because the first 'silent' defect already halves the protection.