§411.7 FELV — functional extra-low voltage
Explain in plain words
FELV is a low-voltage circuit (up to 50 V AC) used for functional reasons — control, signaling, automation — when full safety systems SELV/PELV are not required. Key point: FELV itself is NOT a protection against electric shock, because its source (an ordinary transformer without reinforced insulation) does not guarantee reliable separation from the 230 V mains. Therefore, full protection according to §411 must be provided on the primary side, and the secondary circuit is considered as if it could be at full mains voltage — its insulation and enclosures must be rated for the primary voltage, and enclosures must be connected to PE. FELV connectors are intentionally made incompatible with SELV/PELV sockets to prevent accidental interconnection of different systems. For an electrician, the conclusion is simple: low voltage FELV is not a reason to relax protection, because there is no safe isolation from the mains.