§523.1 Permissible continuous cable rating — reference method
Explain in plain words
I_z is the current a cable can carry continuously without overheating its insulation (70 °C for PVC, 90 °C for XLPE). It is not calculated but taken from IEC 60364-5-52 tables depending on the installation method, denoted by letters: A — in a thermally insulated wall, B — in conduit on a wall, C — directly on a wall, D — in the ground, E/F/G — in air. The tables are given for standard conditions: 30 °C in air or 20 °C in ground, single cable. This is the base value — a starting point: then apply corrections for temperature (§523.6) and grouping of cables (§523.5). In practice: first determine how the cable is installed, take the base I_z from the table, then adjust it for actual conditions, and only then select the circuit breaker with I_n ≤ I_z.