§523.1 Permissible continuous cable rating — reference method

The continuous current-carrying capacity of a conductor `I_z` is the maximum current a core can carry indefinitely under given installation conditions without exceeding the insulation temperature limit (70 °C for PVC, 90 °C for XLPE). Values for `I_z` come from IEC 60364-5-52 (Annex B) tables, based on the **reference installation method**. The standard defines these methods with letter codes: `A1` (insulated conductors in a thermally insulated wall), `A2` (multicore cable in a thermally insulated wall), `B1` (insulated conductors in conduit on a wall), `B2` (multicore cable in conduit on a wall), `C` (single or multicore cable directly on a wall), `D` (cable in ground, including conduit in ground and direct burial), `E` (multicore in free air), `F` (touching single-core in free air), `G` (spaced single-core in free air). Table values apply under **standardized conditions**: ambient temperature 30 °C for air or 20 °C for ground, single circuit, soil thermal resistivity 2.5 K·m/W. The reference method is the entry point for sizing: you take the base `I_z`, then apply correction factors for ambient temperature (§523.6), grouping (§523.5), and other factors. The adjusted `I_z` coordinates with the overload protection device per `I_n ≤ I_z` (§433.1).
EB-authored summary for design convenience — NOT normative IEC text. Official standard IEC 60364-5-52:2009 available at webstore.iec.ch →.
Explain in plain words
In plain words
AI-generated — may contain inaccuracies

I_z is the current a cable can carry continuously without overheating its insulation (70 °C for PVC, 90 °C for XLPE). It is not calculated but taken from IEC 60364-5-52 tables depending on the installation method, denoted by letters: A — in a thermally insulated wall, B — in conduit on a wall, C — directly on a wall, D — in the ground, E/F/G — in air. The tables are given for standard conditions: 30 °C in air or 20 °C in ground, single cable. This is the base value — a starting point: then apply corrections for temperature (§523.6) and grouping of cables (§523.5). In practice: first determine how the cable is installed, take the base I_z from the table, then adjust it for actual conditions, and only then select the circuit breaker with I_n ≤ I_z.