§523.5 Correction factor for grouping of cables of several circuits
Explain in plain words
When several circuits are run together — in a tray, conduit, or bundle — they heat each other and cool worse than a single cable. Therefore, the base permissible current I_z must be multiplied by a grouping reduction factor C_f, less than one. Values are taken from tables based on installation method and number of circuits: for one circuit C_f = 1.0, and for, say, nine bundled together it is about 0.5, meaning the cable can carry half the current. A group is considered cables that touch or are closer than two diameters apart; if spaced further apart, no correction is needed. Practical takeaway: a tightly packed bundle of cables requires either a larger cross-section or a lower load, otherwise the insulation will overheat even at a seemingly normal current.