§523.5 Correction factor for grouping of cables of several circuits

When multiple circuits are laid together in a shared cable space (tray, conduit, ladder, or bundle), adjacent conductors heat each other, and cable cooling degrades compared to single runs. Therefore, the base continuous current rating `I_z` per §523.1 must be multiplied by a grouping correction factor `C_f` < 1.0 — so insulation never hits its temperature limit at a lower actual current. `C_f` values come from Tables B.52.17–B.52.21 of IEC 60364-5-52 (Annex B), depending on installation method, cable spacing, and number of grouped circuits: `C_f = 1.00` for a single circuit and decreases as count rises; a typical value for nine grouped circuits is `C_f ≈ 0.50` (bunched per B.52.17). A group includes circuits within thermal interaction — cables touching or with center-to-center spacing less than 2 diameters (`2 × D_e`); beyond that, grouping does not apply (`C_f = 1.00`). The final derated capacity is multiplicative: `I_z(derated) = I_z(base) × C_f × k_1 × ...` (where `k_1` is the ambient temperature correction per §523.6). This reduced `I_z` is then used for overload protection coordination per §433.1 (condition `I_n ≤ I_z`).
EB-authored summary for design convenience — NOT normative IEC text. Official standard IEC 60364-5-52:2009 available at webstore.iec.ch →.
Explain in plain words
In plain words
AI-generated — may contain inaccuracies

When several circuits are run together — in a tray, conduit, or bundle — they heat each other and cool worse than a single cable. Therefore, the base permissible current I_z must be multiplied by a grouping reduction factor C_f, less than one. Values are taken from tables based on installation method and number of circuits: for one circuit C_f = 1.0, and for, say, nine bundled together it is about 0.5, meaning the cable can carry half the current. A group is considered cables that touch or are closer than two diameters apart; if spaced further apart, no correction is needed. Practical takeaway: a tightly packed bundle of cables requires either a larger cross-section or a lower load, otherwise the insulation will overheat even at a seemingly normal current.