IEC 60364-5-52 · Edition 2009 EB SUMMARY

§523.6 Ambient temperature correction factor

Cable insulation has a fixed operating temperature (PVC — 70 °C, XLPE — 90 °C). The permissible continuous current `I_z` from tables in §523.1 is given for a reference ambient temperature: **30 °C for cables in air** and **20 °C for cables in/on ground**. If the actual ambient temperature differs, the conductor’s thermal headroom for self-heating changes, and the rated `I_z` must be adjusted by a multiplicative factor `k_1` (ambient temperature correction factor). Values of `k_1` come from Annex B tables of IEC 60364-5-52, separately for air and ground, by insulation type (PVC / XLPE). For XLPE, the spread of `k_1` is smaller due to its higher operating temperature of 90 °C versus 70 °C for PVC. At elevated ambient temperatures `k_1 < 1` — `I_z` decreases; at lower temperatures `k_1 > 1` — a limited increase is allowed. This correction is applied together with the grouping factor `C_f` (§523.5): the derived permissible current equals `I_z × k_1 × C_f × ...` (other factors like burial depth, soil thermal resistivity, etc., if present). This derived `I_z` is then used in the coordination `I_B ≤ I_n ≤ I_z` and `I_2 ≤ 1.45 × I_z` per §433.1.
EB-authored summary for design convenience — NOT normative IEC text. Official standard IEC 60364-5-52:2009 available at webstore.iec.ch →.
Explain in plain words
In plain words
AI-generated — may contain inaccuracies

Cable insulation is rated for a certain temperature (PVC — 70 °C, XLPE — 90 °C), and the permissible current tables are given for reference 30 °C in air and 20 °C in ground. If the ambient is warmer — the cable has less 'headroom' for self-heating, so the permissible current must be reduced by multiplying by a factor k_1, less than one; in cooler conditions, a slightly higher current is allowed. The k_1 values are taken from tables separately for air and ground and by insulation type. The correction is applied together with the grouping factor — the multipliers are multiplied. In practice, this is important for hot boiler rooms, attics, or near ovens: there, a cable of the same cross-section carries less current than in normal conditions.