IEC 60364-5-52 · Edition 2009 EB SUMMARY

§523.7 Parallel connection of conductors — uniform current distribution

When a single conductor’s ampacity is insufficient, several cores are paralleled in one circuit. For even current sharing, all parallel conductors must have **identical material** (copper or aluminum), **identical cross-section**, and **practically identical length** — only with geometric symmetry of the electrical paths is each core’s impedance equal, so current divides evenly. **No intermediate taps** between cores are allowed along the parallel set — any tap breaks symmetry and causes uneven current distribution, potentially overloading individual cores while the total circuit current remains within limits. The standard sets **minimum cross-sections for paralleling**: 50 mm² for copper and 70 mm² for aluminum — below these, manufacturing tolerances make uniform distribution practically impossible. Overload protection for the parallel set uses one device rated `I_n` coordinated with the **total** continuous current capacity per §433.1 (conditions `I_B ≤ I_n ≤ I_z(total)` and `I_2 ≤ 1.45 × I_z(total)`); each core must also withstand short-circuit current per §434.5 adiabatic check (`k² × S² ≥ I² × t`). If geometric symmetry can’t be ensured (different length or cross-section), paralleling per §523.7 is not allowed — instead, each core runs as a separate circuit with its own protective device.
EB-authored summary for design convenience — NOT normative IEC text. Official standard IEC 60364-5-52:2009 available at webstore.iec.ch →.
Explain in plain words
In plain words
AI-generated — may contain inaccuracies

When a single cable is insufficient for the current, several conductors are connected in parallel. To ensure current divides equally between them, all conductors must be of the same material, same cross-section, and practically the same length — otherwise, the 'easier' conductor will carry more current and overheat, even if the total current is normal. No intermediate taps are allowed along the parallel set — they break symmetry. The standard sets a minimum cross-section for paralleling: 50 mm² for copper and 70 mm² for aluminum, because uniformity cannot be guaranteed for thinner ones. In practice: if you cannot ensure equal length and cross-section of all conductors — do not parallel; run each line separately with its own protection.