IEC 60364-5-52 · Edition 2009 EB SUMMARY

§525.1 Voltage drop — normative scope and recommended limits (Annex G)

Normative requirement §525 is functional: voltage drop along the installation must keep the voltage at each current-using equipment’s terminals within the limits specified by the relevant product standard. No fixed numerical threshold appears in §525.1 — the standard delegates that to product standards and national codes. Informative **Annex G** gives widely accepted practical limits from the point of connection: **3 % for lighting circuits** and **5 % for other circuits** (sockets, motors, fixed equipment). Calculation formulas for `ΔU` (single- and three-phase, including resistive and reactive components `R` and `X`) are in Annex G — see adjacent article. Exceeding recommended limits has three consequences: (1) equipment may malfunction or draw higher current; (2) cable thermal losses increase; (3) fault current at the endpoint drops, degrading automatic disconnection coordination per §411 (`Z_s × I_a ≤ U_0`). If calculated `ΔU` exceeds Annex G limits, increase conductor cross-section and re-check overload coordination per §433.1.
EB-authored summary for design convenience — NOT normative IEC text. Official standard IEC 60364-5-52:2009 available at webstore.iec.ch →.
Explain in plain words
In plain words
AI-generated — may contain inaccuracies

This clause requires that due to voltage drop in wires, the voltage at each device remains within its allowable limits. No specific number is given in the text itself — it is left to equipment standards and national regulations, but indicative limits are given in informative Annex G: 3 % for lighting and 5 % for other circuits, measured from the supply point. Excessive voltage drop has three consequences: devices work worse and draw more current, the cable heats more, and — importantly — the short-circuit current at the end of the line drops, impairing protection operation. If calculation shows the limit is exceeded — increase the cable cross-section. In practice: on long lines (remote sockets, street lighting, pumps), the cross-section is often determined by voltage drop, not heating.