§525.1 Voltage drop — normative scope and recommended limits (Annex G)
Explain in plain words
This clause requires that due to voltage drop in wires, the voltage at each device remains within its allowable limits. No specific number is given in the text itself — it is left to equipment standards and national regulations, but indicative limits are given in informative Annex G: 3 % for lighting and 5 % for other circuits, measured from the supply point. Excessive voltage drop has three consequences: devices work worse and draw more current, the cable heats more, and — importantly — the short-circuit current at the end of the line drops, impairing protection operation. If calculation shows the limit is exceeded — increase the cable cross-section. In practice: on long lines (remote sockets, street lighting, pumps), the cross-section is often determined by voltage drop, not heating.