IEC 60364-5-55 · Edition 2011+AMD1:2012+AMD2:2016 EB SUMMARY

§551.1 Low-voltage generators — scope of application

Section 551 covers the selection and installation of low-voltage and extra-low-voltage generator sets that supply an electrical installation continuously or intermittently. This includes diesel and gas generators, static UPSs, inverters, and similar sources. The standard defines three operating modes: (a) **standby supply** when mains voltage fails; (b) **island mode** for installations not connected to the public grid; (c) **parallel operation** with the grid (cogeneration, grid-tied PV systems, etc.). Generator electrical characteristics — source impedance, prospective short-circuit current, neutral earthing arrangement — differ significantly from the grid and depend on the source, so protective measure conditions (§411) **must be verified** for generator-fed mode. Grid-parallel PV systems are additionally covered by IEC 60364-7-712 (DC side, anti-islanding protection). Section 551 covers only electrical aspects — earthing, automatic disconnection, overcurrent protection, switching coordination; mechanical issues, fuel systems, and control circuits are outside its scope. Precautions against unintended parallel operation follow IEC 60364-5-53.
EB-authored summary for design convenience — NOT normative IEC text. Official standard IEC 60364-5-55:2011+AMD1:2012+AMD2:2016 available at webstore.iec.ch →.
Explain in plain words
In plain words
AI-generated — may contain inaccuracies

Section 551 covers connection of local power sources — diesel and gas generators, UPS, inverters. It distinguishes three modes: standby supply when mains fails, island mode, and parallel operation with the mains. The key point for an electrician: a generator has different characteristics than the mains — different source impedance, different short-circuit current, sometimes a different neutral earthing scheme, so protection per §411 must be checked separately for generator supply. You cannot assume that protection working from the mains will automatically work from the generator — the generator's short-circuit current is often much lower. The section covers only electrical aspects (earthing, disconnection, switching); fuel, mechanics, and control are outside its scope.