§551.1 Low-voltage generators — scope of application
Explain in plain words
Section 551 covers connection of local power sources — diesel and gas generators, UPS, inverters. It distinguishes three modes: standby supply when mains fails, island mode, and parallel operation with the mains. The key point for an electrician: a generator has different characteristics than the mains — different source impedance, different short-circuit current, sometimes a different neutral earthing scheme, so protection per §411 must be checked separately for generator supply. You cannot assume that protection working from the mains will automatically work from the generator — the generator's short-circuit current is often much lower. The section covers only electrical aspects (earthing, disconnection, switching); fuel, mechanics, and control are outside its scope.