§4.3.5 Categories of application of automatic circuit breakers — A and B
Explain in plain words
This clause divides industrial circuit breakers into two categories based on their ability to 'hold' short-circuit current for selectivity. Category A — without intentional time delay: trip instantaneously on short circuit; these are simple breakers without adjustable short-circuit release. Category B — with intentional short time delay, to allow the downstream device to clear the fault first; they declare I_cw — the current the device can withstand without damage for a specified short time (0.05–1 s). I_cw is the main difference between B and A. In practice: category B is needed at upper distribution levels where time selectivity is important — so that a short circuit in a group does not trip the main breaker of the entire panel. Domestic modular breakers are not covered here — they are governed by another standard (curves B/C/D).