IEC 60947-2 · Edition 2016+AMD1:2019 EB SUMMARY

§4.3.5 Categories of application of automatic circuit breakers — A and B

§4.3.5 splits low-voltage circuit breakers into two application categories based on their ability to hold short-circuit current with intentional delay for selectivity. **Category A** — breakers **without** intentional time delay under short circuit: instantaneous trip, `I_cw` typically not declared. This includes industrial MCCBs without adjustable short-circuit settings (note: residential MCBs fall under IEC 60898-1 with B/C/D curves, not §4.3.5 categories). **Category B** — breakers with **intentional short-time delay** for coordination with downstream protection; `I_cw` (rated short-time withstand current) is mandatory — the RMS short-circuit current the device can withstand without damage for a specified short time (preferred values per §4.3.5.4: 0.05 / 0.1 / 0.25 / 0.5 / 1 s, with 3 s typical for ACBs). Category B covers MCCBs with adjustable electronic trips and air circuit breakers (ACBs); it serves as the upstream tier in time-based selectivity — the upstream device’s delay lets the downstream breaker clear the fault first. All IEC 60947-2 breakers declare `I_cu` and `I_cs` per §8.3.4 (not exclusive to Cat B); `I_cw` is the true differentiator between Cat B and Cat A.
EB-authored summary for design convenience — NOT normative IEC text. Official standard IEC 60947-2:2016+AMD1:2019 available at webstore.iec.ch →.
Explain in plain words
In plain words
AI-generated — may contain inaccuracies

This clause divides industrial circuit breakers into two categories based on their ability to 'hold' short-circuit current for selectivity. Category A — without intentional time delay: trip instantaneously on short circuit; these are simple breakers without adjustable short-circuit release. Category B — with intentional short time delay, to allow the downstream device to clear the fault first; they declare I_cw — the current the device can withstand without damage for a specified short time (0.05–1 s). I_cw is the main difference between B and A. In practice: category B is needed at upper distribution levels where time selectivity is important — so that a short circuit in a group does not trip the main breaker of the entire panel. Domestic modular breakers are not covered here — they are governed by another standard (curves B/C/D).