IEC 60947-2 · Edition 2016+AMD1:2019 EB SUMMARY

§8.3.4 Short-circuit characteristics of circuit breakers — `I_cu` and `I_cs`

§8.3.4 defines two short-circuit ratings for a low-voltage circuit breaker, describing its behavior when interrupting a fault. **`I_cu` (rated ultimate short-circuit breaking capacity)** is the maximum prospective fault current the device can clear **once** per the O–CO test sequence (open — close-open); after that, the breaker remains safe but full operational fitness for further duty is not guaranteed—inspection or replacement may be needed. **`I_cs` (rated service short-circuit breaking capacity)** is the fault current the breaker can clear **repeatedly** (at least three cycles per O–CO–CO sequence) **while retaining full operational fitness** for continued normal service. The relationship is `I_cs ≤ I_cu`; the manufacturer declares `I_cs` as a percentage of `I_cu` from the standard set 25 % / 50 % / 75 % / 100 % (exact minimum ratio depends on category A/B and subclass per §8.3.4.1.2/.1.3). Modern quality MCCBs typically offer `I_cs = 100 % × I_cu` — full service capability. When selecting a device, the prospective fault current at the installation point must not exceed `I_cu`; if operation must continue after a possible fault without repair (critical distribution nodes), `I_cs` becomes the deciding factor. Do not confuse `I_cu` with `I_cw` per §4.3.5.2 — that one describes short-time withstand for category B selectivity without mandatory interruption.
EB-authored summary for design convenience — NOT normative IEC text. Official standard IEC 60947-2:2016+AMD1:2019 available at webstore.iec.ch →.
Explain in plain words
In plain words
AI-generated — may contain inaccuracies

This clause specifies two 'short-circuit' ratings of a circuit breaker. I_cu is the ultimate breaking capacity: the maximum short-circuit current the device can interrupt at least once, remaining safe but possibly requiring inspection or replacement afterward. I_cs is the service breaking capacity: the short-circuit current the device can interrupt repeatedly and remain fully fit for further service. Always I_cs ≤ I_cu, and the manufacturer states I_cs as a percentage of I_cu (25/50/75/100%); in quality modern breakers, I_cs often equals 100% of I_cu. Practical selection rule: the prospective short-circuit current at the installation point must not exceed I_cu; if after a short circuit the equipment must continue working without repair (critical circuits), aim for I_cs. Do not confuse I_cu with I_cw — the latter is about withstand for selectivity, not interruption.