§8.3.4 Short-circuit characteristics of circuit breakers — `I_cu` and `I_cs`
Explain in plain words
This clause specifies two 'short-circuit' ratings of a circuit breaker. I_cu is the ultimate breaking capacity: the maximum short-circuit current the device can interrupt at least once, remaining safe but possibly requiring inspection or replacement afterward. I_cs is the service breaking capacity: the short-circuit current the device can interrupt repeatedly and remain fully fit for further service. Always I_cs ≤ I_cu, and the manufacturer states I_cs as a percentage of I_cu (25/50/75/100%); in quality modern breakers, I_cs often equals 100% of I_cu. Practical selection rule: the prospective short-circuit current at the installation point must not exceed I_cu; if after a short circuit the equipment must continue working without repair (critical circuits), aim for I_cs. Do not confuse I_cu with I_cw — the latter is about withstand for selectivity, not interruption.