§5.3.4 Rated residual operating current of RCDs — standard values `I_ΔN`
Explain in plain words
The standard specifies a range of rated residual operating currents for RCDs (without built-in overcurrent protection): 6, 10, 30, 100, 300, 500, and 1000 mA. This value is the device's rated sensitivity. Based on it, RCDs are divided into two classes. High-sensitivity types (6, 10, 30 mA) protect people from electric shock when touching live parts; the 30 mA threshold is chosen from physiology — at this current, the risk of cardiac arrest is low. Only RCDs ≤30 mA satisfy the additional protection requirement of §415.1. Devices 100–1000 mA protect not people but against fire due to leakage and are used for selectivity with lower-rated RCDs. In practice: for socket outlets and wet areas, install 30 mA for human protection; for the main supply, use 100–300 mA for fire protection and selectivity.