§5.3 Rated insulation voltage U_i and rated impulse withstand voltage U_imp
Explain in plain words
This clause defines two 'insulation' ratings of an assembly (switchgear). U_i is the rated insulation voltage: it sets creepage distances and dielectric test voltages; the operating voltage of each circuit must not exceed U_i (U_e ≤ U_i). U_imp is the rated impulse withstand voltage: the peak surge of standard shape 1.2/50 μs that the insulation must withstand without breakdown; it determines clearances and covers lightning and switching overvoltages. U_imp is selected based on the overvoltage category of the installation location: OV II for final circuits, OV III for distribution, OV IV for the mains supply. In practice: for an electrician, this means the assembly must have insulation characteristics matching the actual network — near the supply, impulse strength requirements are stricter than at final groups.