IEC 61439-1 · Edition 2020 EB SUMMARY

§5.3 Rated insulation voltage U_i and rated impulse withstand voltage U_imp

Standard §5.3 defines two rated insulation parameters for LV switchgear and controlgear assemblies. `U_i` (rated insulation voltage) is the voltage against which requirements for basic insulation are set: creepage distances and dielectric tests. `U_imp` (rated impulse withstand voltage) is the peak value of a standard 1.2/50 µs impulse voltage that the assembly insulation must withstand without breakdown; this parameter determines required clearances and covers overvoltages of atmospheric, switching, or internal system origin. `U_i` must be distinguished from `U_e` (rated operational voltage) — the actual voltage at which the assembly operates in service; the standard requires `U_e ≤ U_i` for each circuit within the assembly. `U_i` testing uses 50/60 Hz AC for 60 seconds; `U_imp` is verified with a 1.2/50 µs impulse. Selecting `U_imp` depends on the overvoltage category of the installation location per IEC 60664-1 and IEC 60364-4-44 — category is determined by equipment position in the electrical installation (OV II — final circuits after the main distribution board, OV III — distribution circuits, OV IV — equipment at the service entrance from the public network).
EB-authored summary for design convenience — NOT normative IEC text. Official standard IEC 61439-1:2020 available at webstore.iec.ch →.
Explain in plain words
In plain words
AI-generated — may contain inaccuracies

This clause defines two 'insulation' ratings of an assembly (switchgear). U_i is the rated insulation voltage: it sets creepage distances and dielectric test voltages; the operating voltage of each circuit must not exceed U_i (U_e ≤ U_i). U_imp is the rated impulse withstand voltage: the peak surge of standard shape 1.2/50 μs that the insulation must withstand without breakdown; it determines clearances and covers lightning and switching overvoltages. U_imp is selected based on the overvoltage category of the installation location: OV II for final circuits, OV III for distribution, OV IV for the mains supply. In practice: for an electrician, this means the assembly must have insulation characteristics matching the actual network — near the supply, impulse strength requirements are stricter than at final groups.