§5.4 Rated Diversity Factor (RDF)
Explain in plain words
The rated diversity factor (RDF) accounts for the fact that not all circuits in an assembly are fully loaded simultaneously. The assembly manufacturer declares the RDF, and by default it is taken as: 1 circuit — 1.0; 2–3 — 0.9; 4–5 — 0.8; 6–9 — 0.7; 10 or more — 0.6. It is used to check the loading of busbars and the incoming device: the design current is the sum of the ratings of outgoing circuits multiplied by the RDF, not the simple sum of all breakers. This prevents oversizing the busbars and incoming device for an unrealistic scenario where everything is on. In practice: without RDF, an assembly with many groups would be excessively 'heavy'; but if all circuits actually operate simultaneously (e.g., purely process loads), the RDF should be taken closer to 1.0.