§8.5.3 Internal separation of an assembly — Forms 1-4

Internal separation of an assembly (switchgear and controlgear assembly) is the physical partitioning between busbars, functional units (FUs), and terminals for external conductors. It protects personnel from **direct contact** with live parts during maintenance when voltage is partially removed. §8.5.3 of IEC 61439-1 establishes the general concept; the detailed Forms 1–4 classification for PSC-Assemblies is given in IEC 61439-2 §8.101 (and for DBO in IEC 61439-3). The separation level is **subject to agreement between the manufacturer and the user** (default is Form 1 if no agreement exists). **Form 1** — no internal separation; all parts share one compartment. **Form 2** — busbars separated from functional units; subdivided into `2a` (terminals not separated from busbars) and `2b` (terminals separated from busbars). **Form 3** — functional units additionally separated from each other; `3a` keeps terminals with busbars, `3b` separates them. **Form 4** — highest level: busbars, functional units, and external cable terminals all separated; `4a` — terminals in the respective functional unit compartment, `4b` — terminals in their own separate compartment. Higher Forms reduce direct contact risk with adjacent live parts during servicing or replacement of one functional unit, but increase cost and enclosure size (internal arc protection is a separate topic, IEC TR 61641). The chosen Form must be documented in the manufacturer’s documentation.
EB-authored summary for design convenience — NOT normative IEC text. Official standard IEC 61439-1:2020 available at webstore.iec.ch →.
Explain in plain words
In plain words
AI-generated — may contain inaccuracies

Internal separation refers to physical partitions inside the assembly between busbars, functional units, and terminals, so that during maintenance under partial voltage, a person cannot access adjacent live parts. The standard defines levels from Form 1 to Form 4: Form 1 — no separation, everything in one compartment; Form 2 — busbars separated from units; Form 3 — units also separated from each other; Form 4 — the highest level, where busbars, units, and external cable terminals are all separated. The level is a matter of agreement between manufacturer and customer (default is Form 1). Higher forms are safer during maintenance but more expensive and larger. In practice: if groups in the assembly need to be serviced or changed while the rest remains live, order a higher separation form — it directly affects work safety.