§8.5.3 Internal separation of an assembly — Forms 1-4
Explain in plain words
Internal separation refers to physical partitions inside the assembly between busbars, functional units, and terminals, so that during maintenance under partial voltage, a person cannot access adjacent live parts. The standard defines levels from Form 1 to Form 4: Form 1 — no separation, everything in one compartment; Form 2 — busbars separated from units; Form 3 — units also separated from each other; Form 4 — the highest level, where busbars, units, and external cable terminals are all separated. The level is a matter of agreement between manufacturer and customer (default is Form 1). Higher forms are safer during maintenance but more expensive and larger. In practice: if groups in the assembly need to be serviced or changed while the rest remains live, order a higher separation form — it directly affects work safety.