Cross-section calculation cable
Online cable cross-section calculator by power and current according to IEC 60364 and the app's reference table. Considers installation method, conductor material, and permissible voltage drop.
Input data
Result
How to calculate cable cross-section?
Proper selection of cable cross-section is the basis of safe electrical wiring. A cable that is too thin overheats, which can lead to fire. One that is too thick results in unnecessary material costs.
Cable cross-section is selected based on two criteria: permissible current (according to the app's reference table and IEC 60364) and permissible voltage drop (usually up to 5%, recommended up to 3% for lighting circuits).
Permissible current depends on the installation method: a cable in a wall duct (A2) dissipates heat worse than a cable laid openly on a wall (C), so the permissible current is lower. A copper cable can carry more current than an aluminium cable of the same cross-section.
This calculator automatically selects the standard cable cross-section considering both criteria, installation method, and conductor material.
Cable cross-section calculation formula
By criterion allowable current — cross-section is selected from the app's reference table depending on the installation method and material (the source of the figures is not verified).
By criterion voltage drop: S = ρ × k × L × I / (U × ΔU%/100), where S — cross-section (mm²), ρ — resistivity (Cu: 0.0225, Al: 0.036 Ω·mm²/m at 70 °C), k = 2 for single-phase or √3 for three-phase, L — length (m), I — current (A), U — voltage (V), ΔU% — permissible voltage drop.
Example: line 40 m, 5 kW (220V, 1ph), Cu, ΔU≤5%. Current: 5000/(220×0.95) ≈ 23.9 A → by current, 4 mm² needed (27A). By voltage drop: S = 0.0225×2×40×23.9/(220×0.05) = 3.91 mm² → standard 4 mm². Result: 4 mm².
Frequently asked questions about cable cross-section
Is 'cable cross-section' the same as 'cable gauge'?
Yes, cross-section and gauge are synonyms. Both refer to the cross-sectional area of the current-carrying conductor in mm². In IEC 60364 and IEC standards, the official term is 'cross-section', while in common speech and some older sources, 'gauge' is used. In both cases, the same values are meant: 1.5 mm², 2.5 mm², 4 mm², 6 mm², 10 mm², 16 mm², etc.
How to calculate cable cross-section based on load power?
First calculate the operating current: I = P / (U × cosφ). For single-phase 220V and resistive load (cosφ=1): I = P (kW) × 4.55. Example: a 2 kW water heater → I ≈ 9 A → cross-section 1.5 mm² (copper, in wall, permissible current 19 A — with margin). An electric stove 7 kW → I ≈ 32 A → cross-section 6 mm². The calculator performs this calculation automatically — enter power in kW, get the recommended cross-section verified by two criteria: permissible current and voltage drop.
What cable cross-section is needed for an apartment with single-phase supply up to 10 kW?
For the incoming cable — 6 mm² (copper), if longer than 25 m from the meter — 10 mm². For socket circuits — 2.5 mm² (MCB B16 or C16), for lighting — 1.5 mm² (MCB B10). Values for installation in wall (method A2) per the app's reference table.
Why does the installation method affect cable cross-section selection?
A cable in a wall (A2) is surrounded by masonry and dissipates heat poorly, so its permissible current is lower. For example, a 2.5 mm² Cu cable in a wall can carry 21 A, while surface-mounted (C) — 27 A. If cross-section is chosen without considering the installation method, the cable may overheat even under normal load.
When does voltage drop determine the cross-section rather than permissible current?
On long runs — from 30–50 m and beyond. For example, to power a garage 40 m away with 5 kW load, 2.5 mm² is sufficient for current, but 6 mm² is needed for voltage drop. If this criterion is ignored, equipment receives reduced voltage, shortening its lifespan.
Copper or aluminium — which to choose for internal wiring?
For internal wiring, IEC 60364 recommends copper cable. Copper has lower resistivity (0.0225 vs 0.036 Ω·mm²/m at 70 °C), can carry higher current for the same cross-section, is more flexible and durable. Aluminium is suitable for large incoming cables (from 16 mm²).
What cable is needed for an electric stove or oven?
For an electric stove 7–8 kW (single-phase) — cable 6 mm² (Cu) with MCB C32. For a built-in oven up to 3.5 kW — a separate circuit 2.5 mm² with MCB C16. Both for installation in wall. Always run a separate line from the distribution board.
How to select cable cross-section based on load current?
Calculate the operating current: I = P / (U × cosφ) for single-phase or I = P / (√3 × U × cosφ) for three-phase. Find in the ampacity table a cross-section whose permissible current ≥ I. In wall (A2), permissible current is 20–30% lower than surface-mounted (C).
Is this calculator suitable for DC cable calculation?
The basic logic can be used: cosφ = 1, coefficient k = 2 always (two conductors — plus and minus). Permissible current tables for DC cables differ slightly from IEC AC tables. For battery systems and solar panels, check against the manufacturer's DC cable specifications.
Tools
Related tools
MCB selection by load
Breaker rating and trip curve selection (B/C/D) with coordination and selectivity check.
Voltage drop calculator
Voltage drop calculation in cable with visualization and cross-section comparison.
Converter W ↔ A ↔ V
Convert watts to amps for 1ph, 3ph and DC grids. Cos φ, recommended MCB and cable cross-section.
Design electrical panels online
ElectroBoard — electrical panel designer with automatic validation per IEC 60364, load calculation, and PDF export. Free.