ElectroBoard
/Tools/RCD / RCBO selection
Open constructor →
🛡 CALCULATOR

Selection RCD / RCBO

Online calculation and selection of type, rating, and differential current of RCD or RCBO based on room type, earthing system, and load according to IEC 60364.

⚙️ Parameters

Determines ΔI and RCD type
Affects the possibility of using an RCD
🛡
RCD AC 25/30 mA
Residual current device typeAC
Residual current (ΔI)30 mA
Rated current25 A
Poles2P (1P+N)
Number of groups3 (max. ∼2 by leakage)
Device typeRCD + separate MCBs
Type AC: Protection against sinusoidal AC residual current
Standard protection — 30 mA type AC or A per IEC 60364-4-41
⚠️
TN-C-S: PEN split into N and PE at the distribution board. RCD mandatory (IEC 60364-4-41).

RCD types — comparison

TypeProtects againstApplicationCost
AC Sinusoidal AC residual currentLighting, simple household appliances
A AC + pulsating DCInverter appliances, kitchen, bathroom€€
B AC + DC + smooth DCIT equipment, EV chargers, server rooms€€€
S AC (with 40 ms delay)Incoming fire-protection RCD (300 mA)€€

How to calculate the rated current for an RCD

The rated current of the RCD is selected by the formula:

I = P / (U × cos φ)

where: P — load power in watts, U — mains voltage (220 V for single-phase), cos φ — power factor (0.95 for household appliances).

Example: bathroom — washing machine 2.2 kW + heated floor 1.5 kW = 3.7 kW.
I = 3700 / (220 × 0.95) = 17.7 A → select RCD 25 A (next standard rating above MCB C20). ΔI = 10 mA, type A (bathroom zone).

Key rule: the RCD rating must be not less than the rating of the protective MCB on the same line. If the MCB is C25 — the RCD is taken at 25 A or 32 A. A lower RCD rating will cause nuisance tripping at full load.

How to choose an RCD for an apartment or house?

RCD — residual current device — protects against electric shock and fire due to leakage current. RCBO (residual current circuit breaker with overcurrent protection) is an RCD + MCB in one housing.

Key parameters for selection: differential current (ΔI) — 30mA for human protection, 10mA for bathrooms, 300mA for fire protection; and type — AC for simple loads, A for inverter equipment, B for server equipment.

The RCD rating is chosen not less than the rating of the upstream MCB. For example, if the line has a C25 MCB, the RCD must be 25A or higher.

The number of groups under one RCD is limited by the total leakage current — it must not exceed 1/3 of ΔI. Typical leakage is 3-5 mA per group, so for a 30mA RCD, no more than 2-3 groups are recommended.

Frequently asked questions about RCDs and RCBOs

Which is better — separate RCD with MCBs or RCBO?+
Both provide the same level of protection. RCD + MCBs are cheaper and easier to diagnose: you can immediately see whether it was leakage or overload protection that tripped. RCBO is more compact (2 modules instead of 4) — convenient for small distribution boards.
Why does the RCD trip without apparent reason?+
Most common reasons: too many circuits under one RCD (total background leakage exceeds 10 mA for a 30 mA RCD), moisture in socket-outlets, old cable with micro-damage to insulation, or a faulty appliance. For diagnostics, disconnect circuits one by one.
When is it mandatory to install Type A RCD instead of AC?+
Type A is required for circuits with inverter equipment: washing machines and dishwashers with inverter motors, air conditioners, induction hobs, electric vehicle charging stations. These devices can generate pulsating DC leakage current, to which Type AC RCD does not respond.
Why is a 100–300 mA fire protection RCD needed at the incoming supply?+
A fire protection RCD (100–300 mA, Type S — selective) protects against fire caused by significant leakage current in wiring that is not detected by 30 mA group RCDs. It does not protect against electric shock — for that, 30 mA group RCDs are required.
How many circuits can be connected under one 30 mA RCD?+
It is recommended not to exceed 2–3 circuits. Each circuit has a background leakage of 3–5 mA. The total leakage should not exceed 1/3 of ΔI, i.e., 10 mA for a 30 mA RCD. With 4+ circuits, the risk of nuisance tripping increases.

Related tools

🛡
MCB selection by load
Breaker rating and trip curve selection (B/C/D) with coordination and selectivity check.
🔌
Cable cross-section calculation
Cable cross-section selection by power, current and installation method per IEC 60364-5-52.
🌈
Wire Colors
Wire color marking table per IEC 60446. Comparison with legacy and North American standards.
← All tools (13)

Automatic RCD selection in the panel builder

In ElectroBoard — 22 device types including RCDs and RCBOs, automatic validation and coordination check.

Design panel →