ElectroBoard
IEC
IEC 60364-5-52 · Edition 2009

§Annex_G Annex G (informative) — Recommended voltage drop limits and calculation examples EB SUMMARY

Annex G is **informative** — it doesn’t set mandatory thresholds, but gives widely accepted design practice benchmarks that typically satisfy the functional requirement of §525.1. **Recommended**: up to **3 %** for lighting circuits and up to **5 %** for other final circuits (sockets, motors, fixed equipment), measured from the point of supply. National codes or product standards may impose stricter limits. To account for reactive load, the full calculation is: `ΔU = K × I_B × L × (cosφ × R + sinφ × X)`, where `K` is the system factor (2 for single-phase L-N, √3 for three-phase balanced), `R` is the conductor AC resistance per unit length, `X` is the inductive reactance per unit length (from cable manufacturer). For purely resistive loads (`cosφ ≈ 1.0`), the `sinφ × X` term drops out. Annex G includes worked examples following the sequence: select installation method → base `I_z` → apply correction factors (§523.5 grouping, §523.6 temperature) → check `I_n ≤ I_z` → check `ΔU`. **Starting voltage dip** for motors and high-inrush loads must be checked separately — steady-state compliance with Annex G does not guarantee acceptable dip during start-up.
EB-authored summary for design convenience — NOT normative IEC text. Official standard IEC 60364-5-52:2009 available at webstore.iec.ch →.
💡 Explain in plain words
In plain words
AI-generated — may contain inaccuracies

Annex G is informative, meaning it does not set mandatory figures but gives commonly accepted guidelines that usually satisfy the requirement of §525.1: up to 3 % voltage drop for lighting and up to 5 % for other final circuits, measured from the supply point. It also provides the formula: ΔU = K × I_B × L × (cosφ × R + sinφ × X), where K is 2 for single-phase and √3 for three-phase, and R and X are the cable's resistance and reactance. For a purely resistive load, the term with X disappears and the formula simplifies. Voltage dip during motor starting is checked separately — steady-state within limits does not guarantee no dip during startup. In practice: this annex is used when calculating cross-sections for long lines manually.