Panel Templates
When you create a new project you can start from one of 4 ready-made templates. Each template ships a typical panel layout with pre-configured devices, connections, cables, and consumers.
🏠 1-Bedroom Apartment
Parameters: single-phase, TN-C-S, 5 kW
A simple panel for a small apartment. Two rails of 12 modules each.
Rail 1 — Incomer:
- Main MCB 32 A (curve C)
- Main RCD 40 A / 30 mA (type AC)
Rail 2 — Groups (under the RCD):
- Lighting — 10 A, curve B, 1.5 mm² cable (in wall, 20 m)
- Room sockets — 16 A, curve C, 2.5 mm² cable (in wall, 15 m)
- Kitchen sockets — 16 A, curve C, 2.5 mm² cable (in wall, 12 m)
- Water heater — 16 A, curve C, 2.5 mm² cable (in wall, 8 m)
- Washing machine — 16 A, curve C, 2.5 mm² cable (in wall, 10 m)
🏢 2-Bedroom Apartment
Parameters: single-phase, TN-C-S, 7 kW
An extended panel with two RCDs — a dedicated one for wet zones. Rails of 18 + 18 modules.
Rail 1 — Incomer:
- Main MCB 40 A (curve C)
- "Wet zones" RCD 40 A / 30 mA — for the bathroom, water heater, and washing machine
- "General" RCD 40 A / 30 mA — for the remaining circuits
Rail 2 — Groups:
Under the "wet zones" RCD:
- Bathroom — 16 A, 2.5 mm² cable
- Water heater — 16 A, 2.5 mm² cable
- Washing machine — 16 A, 2.5 mm² cable
Under the "general" RCD:
- Lighting — 10 A, curve B, 1.5 mm² cable
- Room 1 sockets — 16 A, 2.5 mm² cable
- Room 2 sockets — 16 A, 2.5 mm² cable
- Kitchen sockets — 16 A, 2.5 mm² cable
🏡 3-Phase House
Parameters: three-phase, TN-C-S, 15 kW
A full three-phase panel for a private house. Three rails of 18 modules each, with the load distributed across the phases.
Rail 1 — Incomer:
- Main MCB 40 A (3P, curve C)
- RCD L1 — 40 A / 30 mA
- RCD L2 — 40 A / 30 mA
- RCD L3 — 40 A / 30 mA
Rail 2 — Groups L1 + L2:
Phase L1 (under RCD L1):
- Floor 1 lighting — 10 A, curve B, 1.5 mm² cable (20 m)
- Living-room sockets — 16 A, curve C, 2.5 mm² cable (15 m)
- Water heater — 16 A, curve C, 2.5 mm² cable (8 m)
Phase L2 (under RCD L2):
- Floor 2 lighting — 10 A, curve B, 1.5 mm² cable (25 m)
- Kitchen sockets — 16 A, curve C, 2.5 mm² cable (12 m)
- Washing machine — 16 A, curve C, 2.5 mm² cable (10 m)
Rail 3 — Groups L3:
Phase L3 (under RCD L3):
- Bedroom sockets — 16 A, curve C, 2.5 mm² cable (18 m)
- Oven — 20 A, curve C, 4 mm² cable (10 m)
- Outdoor lighting — 10 A, curve B, 1.5 mm² cable (30 m, underground)
🔧 Garage / Workshop
Parameters: single-phase, TN-C-S, 5 kW
A compact single-rail panel (12 modules). Cables are run in conduit (method B2); the workbench breaker uses curve D to ride out tool inrush currents.
Rail 1:
- Main MCB 25 A (curve C)
- RCD 40 A / 30 mA
- Lighting — 10 A, curve B, 1.5 mm² cable (in conduit, 15 m)
- Sockets — 16 A, curve C, 2.5 mm² cable (in conduit, 10 m)
- Workbench / power tools — 16 A, curve D, 2.5 mm² cable (in conduit, 8 m)
Using a Template
- Click New project in the project list
- Select a template
- The project is created with all devices, connections, and N busbars for each RCD group
- Adapt it to your needs: add or remove circuits, change ratings, cables, and consumers
Templates are a starting point, not a final solution. Every installation has its own specifics.